CFL-32/2000pd
Power Cable Fault Location System

PURPOSE:

  • Insulation testing of power cables with DC voltage up to 32 kV.
  • Field of application: power cable lines (CL) with a nominal voltage of 380 V…35 kV with paper-oil insulation (PILC), rubber, PVC, as well as cross-linked polyethylene (XLPE) insulation.
  • Preliminary damage localization using a reflectometer with a touch control screen (TDR, ICE and MIM methods).
  • High-voltage pulse generator with discharge energy up to 2000 J (4000 J – instantaneous).
  • Advanced security systems.

Description

DTDR-100 Reflectometer

DTDR-100 is a high-class reflectometer with a sampling frequency of 400 MHz and a range of up to 100 km, which is designed to measure the total length of the cable and the distance to the place of damage of the cable with low transient resistance or wire break. Together with the high-voltage pulse generator HVIG-32 and the MIM MIMCU-32 connecting block, the DTDR-100 can also perform preliminary localization of high-resistance damaged power lines.

DTDR-100 is an easy-to-use and controllable device that, in addition to the touch screen, also supports button control, has a friendly interface and is used for preliminary localization of a damaged cable at a long distance.

  • Sampling frequency 400 MHz.
  • Low-voltage pulse method (TDR).
  • Impulse current method (ICE).
  • Multipulse method (MIM).
  • Two control modes (touch screen/button).
  • Storage of reflexograms and their subsequent printing.
  • Comparison of two or three reflectograms.
  • Data base protocol software.

HVIG-32 High-voltage pulse generator

The high-voltage pulse generator HVIG-32 is used to provide a signal source for preliminary and accurate localization of the place of damage to the KL. Together with the DTDR-100 reflectometer and the MIM MIMCU-32 connection unit, it easily solves the following:

  • Preliminary localization of damage by ICE and MIM methods.
  • Detection of damaged KL by acoustic magnetic method with PP-4 receiver.

MIMCU-32 Connection block MIM

The MIM MIMCU-32 connection block is designed to work with the HVIG-32 high-voltage pulse generator and the DTDR-100 reflectometer for preliminary localization of damaged high resistance cables, including damage due to leakage, flash, low resistance and conductor breakage.

The MIMCU-32 is used to provide multi-pulse method (MIM) signal coupling for the DTDR-100 reflectometer. It uses a new MIM method to simplify the estimation of the shape of the cable damage signal. It can convert the complex form of the breakdown signal during voltage surges into a simple fault signal form that is easy to recognize.

  • Provides the MIM function for preliminary localization.
  • Impulse balancing technology: it is easy to distinguish the malfunction display.
  • Simplicity in operation.
  • Safe design.
  • Isolation between measuring and OV circuits.
  • Closed case without exposed OB components.

PP-4 Receiver

PP-4 is an easy-to-use device that is used to accurately determine the location of damage to the KL. It integrates the function of the acoustic method of magnetic synchronization, the method of determining the strength of the magnetic field to ensure accurate localization.

  • Excellent acoustic quality and noise immunity.
  • Intelligent acoustically magnetic method.
  • Automatic mute function to protect your ears.
  • Bright reflective display.
  • Left/right cable indication.

CL-15/6 Pathfinder

CL-15/6 is a highly effective system for locating underground metal pipes. It consists of a transmitter and a receiver and can be used for tracing, investigating pipes and measuring the depth of underground cables and metal pipes. It can also be used to determine the cable from the bundle, to detect damaged pipe insulation and to close the grounding cable.

  • Color compass for orientation.
  • Ultra-high frequency band of 2 Hz.
  • Indication of correct and false tracking.
  • Precise depth determination in real time.
  • Warning about signal distortion.
  • Highly efficient transmission clamp.
  • Digital schemes of data processing.

TECHNICAL CHARACTERISTICS

DTDR-100 Reflectometer

Work mode TDR (low voltage pulse method),
ICE (impulse current method),
MIM (multipulse method)
Range of signal gain adjustment 70 dB
Low voltage pulse discharge 30 V
Distance measurement range 0…100 km
Resolution 0.1 m
Distance measurement error ± (0.5% × L + 1 m)
Blind zone range 2 m
Low voltage pulse width 40 ns…20.5 µs
Wave speed adjustment range 100 m/ms…300 m/ms
Sampling frequency 400 MHz (real-time sampling)
Number of results to save 100 pcs.
Communication interface USB, Bluetooth (optional)
General Information
Power options 7.4 V, 6000 mAh (Li-ion battery)
Balance time more than 10 hours
Charger 220 V AC, 50 Hz, 2 A, charging time 6 hours
Overall dimensions 274 × 218 × 81 mm
Mass 2.6 kg (main unit)
Working conditions -25…+45 ℃, 5…90 RH (25 ℃), H < 4500 m

 

HVIG-32 High-voltage pulse generator

Impulse voltage range 0…32 kV, step
Maximum pulse energy 2000 J
Built-in capacitor 4 µF
General Information
Power options 220 V AC, 50 Hz
Overall dimensions 400 x 460 x 300 mm
Mass 25 kg
Working conditions -25…+45 ℃, 5…90 RH (25 ℃), H < 4500 m

 

MIMCU-32 MIM Connection Unit

Impulse voltage range 0…32 kV
Input pulse energy below 4000J (instantaneous) and average should be below 2000J
Width of impulse voltage 300 V
Pulse period above 5 s
General Information
Power options 220 V AC, 50 Hz
Overall dimensions 419 x 320 x 341 mm
Mass 10 kg
Working conditions -25…+45 ℃, 5…90 RH (25 ℃), H < 4500 m

 

PP-4 Receiver

Acoustic method of magnetic synchronization
Bandwidth full bandwidth: 80…1500 Hz
low pass: 80…400 Hz
high pass: 200…1500 Hz
bandwidth: 150…600 Hz
Signal gain ≥ 80 dB
Accuracy 0.1 m
Background noise suppression mode support, absence and adaptive suppression
Display LCD display, 800 x 470 dots
General Information
Power options 3.7 V, 6700 mAh (Li-ion battery)
Balance time more than 9 hours
Charger input 220 V AC ± 10 %, 50 Hz; output 8.4 V, 5 V / 2 A
Overall dimensions 230 x 127 x 55 mm
Mass 1 kg (main unit), 1.4 kg (sensor)
Working conditions -25…+45 ℃, 5…90 RH (25 ℃), H < 4500 m

 

*CL-15/6 Pathfinder

Transmitter
Transmission mode direct connection, clamp connection, radiation, booster
Output frequency 640 Hz, 1280 Hz, 8 kHz, 33 kHz, 82 kHz, 197 kHz
Power output 0…15 W, 10 adjustment levels
Impedance matching fully automatic
Surge and current protection fully automatic
Display Dot matrix color LCD display,
320 × 240 dots
Protection class IP 65
Power options 7.4 V, 6000 mAh (Li-ion battery)
Charger input 100…240 V AC, 50/60 Hz; output 8.4 V, 2 A
Overall dimensions 280 x 220 x 90 mm
Mass 2.3 kg
Working conditions -25…+60 ℃, 5…90 RH (25 ℃), H < 4500 m
Receiver
Reception mode direct connection, clamp connection, radiation, booster
Detection mode wide peak, narrow peak, trough value, historical curve, frequency spectrum
Active frequencies 640Hz, 1280Hz, 8kHz, 33kHz, 82kHz, 197kHz
Passive frequencies 50/60 Hz power supply frequency,
4…24 kHz radio frequency
Display Dot matrix color LCD display,
320 × 240 dots, with anti-reflective coating
Degree of protection IP 65
Power options 7.4 V, 3000 mAh (Li-ion battery)
Charger input 100…240 V AC, 50/60 Hz; output 8.4 V, 2 A
Overall dimensions 680 x 120 x 277 mm
Mass 2.0 kg
Working conditions -25…+60 ℃, 5…90 RH (25 ℃), H < 4500 m

* Additional equipment upon agreement with the customer