D100
Insulation Diagnostic System

ADVANTAGES

  • Dissipation/power factor and capacitance testing of power transformers, reactors, instrument transformers, bushings, switches, surge arresters, capacitors.
  • Test voltage up to 12 kV.
  • Output power 2400 VA.
  • Frequency 15…400 Hz.
  • High accuracy of field measurements with high-interference environments.
  • Temperature correction of dissipation/power factor.
  • Fast measurements with adaptive filtering of the interference currents.
  • Safe operation with safety switch, emergency stop, grounding control.
  • Small size and low weight (27 kg).

Description

D100 measures the capacitance and dissipation/power factor, excitation current, transformer turns ratio with the test voltage up to 12 kV.

For a more detailed analysis, the device makes it possible to obtain the dependence dissipation/power factor on frequency (frequency sweep) and voltage (tip-up).

TECHNICAL SPECIFICATIONS:

Value Range Resolution Accuracy
Dissipation factor 0…10 000 % 0.001 % ± (0.5 % rdg + 0.01 %) *
Power factor 0…100 % 0.001 % ± (0.5 % rdg + 0.01 %) *
Capacitance 6 pF…6 μF 0.01 pF ± (0.1 % rdg + 0.1 pF)
Inductance 2 H…2 MH 0.1 mH ± (0.5 % rdg + 1 mH)
Test voltage 100…12000 V 1 V ± (0.3 % rdg + 1 V)
Test current 20 μA…200 mA 0.1 μA ± (0.3 % rdg + 1 μA)
Real power 0…400 W 0.1 mW ± (0.8 % rdg + 1 mW)
Test frequency 15…400 Hz 0.01 Hz ± (0.1 % rdg + 0.1 Hz)

* Tolerances are determined for 45…70 Hz frequency range of the test voltage
Output power 2400 VA
Output voltage 100…12000 V (45…70 Hz)
100…4000 V (15…400 Hz)
Output current <100 mA (continuously)
<200 mA (2 min ON. 8 min OFF)
Power supply 110…240 V. 50/60 Hz
Dimensions 546 × 347 × 247 mm
Weight 27 kg
Safety and EMC EN 61010-1:2010
EN 61326-1:2013

 

 