D100 measures the capacitance and dissipation/power factor, excitation current, transformer turns ratio with the test voltage up to 12 kV.
For a more detailed analysis, the device makes it possible to obtain the dependence dissipation/power factor on frequency (frequency sweep) and voltage (tip-up).
TECHNICAL SPECIFICATIONS:
| Value | Range | Resolution | Accuracy |
| Dissipation factor | 0…10 000 % | 0.001 % | ± (0.5 % rdg + 0.01 %) * |
| Power factor | 0…100 % | 0.001 % | ± (0.5 % rdg + 0.01 %) * |
| Capacitance | 6 pF…6 μF | 0.01 pF | ± (0.1 % rdg + 0.1 pF) |
| Inductance | 2 H…2 MH | 0.1 mH | ± (0.5 % rdg + 1 mH) |
| Test voltage | 100…12000 V | 1 V | ± (0.3 % rdg + 1 V) |
| Test current | 20 μA…200 mA | 0.1 μA | ± (0.3 % rdg + 1 μA) |
| Real power | 0…400 W | 0.1 mW | ± (0.8 % rdg + 1 mW) |
| Test frequency | 15…400 Hz | 0.01 Hz | ± (0.1 % rdg + 0.1 Hz) |
* Tolerances are determined for 45…70 Hz frequency range of the test voltage |
|||
| Output power | 2400 VA | ||
| Output voltage | 100…12000 V (45…70 Hz) 100…4000 V (15…400 Hz) |
||
| Output current | <100 mA (continuously) <200 mA (2 min ON. 8 min OFF) |
||
| Power supply | 110…240 V. 50/60 Hz | ||
| Dimensions | 546 × 347 × 247 mm | ||
| Weight | 27 kg | ||
| Safety and EMC | EN 61010-1:2010 EN 61326-1:2013 |
||