Description
PCFL-12/600 Portable Cable Fault Location Trolley
The PCFL-12/600 is designed for high-voltage direct current insulation testing of power cables, insulation breakdown on damaged cable sections using direct current, pre-locating of cable faults with an aid of the integrated reflectometer using a TDR (Time Domain Reflection), MIM (Multi Impulse Method) and ICE (Impulse Current Method) methods and pinpointing cable faults with an acoustic method.
Reflectometer has 200 MHz sampling rate, supports both touchscreen & one button operation. The display is 17-inch sunny screen. The control knob operation is reduced to the important and essential steps and runs fully automatically. The new hardware with improved sampling frequency, pulse width, impulse altitude ensures 60 km maximum range, highest resolution, accuracy. Three stages HV Impulse Generator with maximum 576 J provides necessary power for accurately acoustic-magnetic pinpointing.
TECHNICAL SPECIFICATIONS
| Reflectometer | |
| Pre-location methods | TDR, MIM, ICE |
| Fault detection range | 5 m…60 km, v/2 = 80 m/μs |
| Resolution | 0.4 m @ v/2 = 80 m/μs |
| Accuracy | ± (0.5 % × L + 1 m) |
| Propagation velocity (v/2) | 10…149.9 m/μs |
| Sampling rate | 200 MHz |
| Gain | -20…+40 dB |
| Pulse width / Amplitude | 100 ns…10 μs / 120 V |
| Compensation | 120 Ohm |
| Display | Touchscreen LCD, 17″ color TFT XGA, sunny 1024×768 |
| Operation system | Linux |
| Data storage | 32 Gb |
| Connection interface | USB, BNC |
| Operation | touchscreen and control knob |
| Rechargeable Battery | 12 V DC |
| HV Impulse Generator | |
| Output DC voltage | 0…12 kV |
| Surge energy | 576 J @ 12 kV |
| Surge rate | 3..8 s, single shot |
| Integrated capacitor | 8 μF |
| GCU-3 Safety monitoring modular | |
| Step voltage monitoring | Monitoring earth to metal chassis |
| Earth loop resistance monitoring | Monitoring system earth to substation earth, auxiliary earth to substation earth |
| Emergency off monitoring | Monitoring the status of Emergency off button |
| Discharge monitoring | For safe discharging, controlled forced discharge |
| Safety key-switch monitoring | Monitoring Key-switch, only with key |
| Temperature monitoring | Overheat measurement |
| Fault diagnosis | Fault code by self-check |
| General | |
| Power supply | 230 V AC ± 15 %, 50/60 Hz, 1.2 kVA |
| Protection class | IP54 |
| Dimensions | 700×600×1000 mm |
| Weight | 31 kg |