Description
The CTVan Cable Test and Fault Location Van offers a comprehensive solution designed for testing cable lines within the voltage range of 0.4 kV to 10 kV, accurately providing pinpoint areas of cable faults. Structurally, it encompasses both an operator’s compartment and a dedicated high-voltage compartment.
A distinct control rack serves as the demarcation between the operator’s compartment and the high-voltage section. This control rack hosts essential control components of the electrical laboratory, alongside display elements that facilitate real-time monitoring of test parameter values.
Furthermore, based on the specific preferences and needs of our esteemed Customers, the electrical laboratory can be further enhanced with supplementary equipment, thoughtfully integrated to align precisely with unique requirements.
TECHNICAL SPECIFICATIONS:
| AC and DC voltage testing (VU-50 testing unit) |
|
| AC voltage range | 50 kV |
| DC voltage range | 60 kV |
| Accuracy of voltage measurement | ±3 % |
| Output current measuring range | 1.0 / 10 mA |
| Accuracy of current measurement | ±5 % |
| Power | 2.5 kW |
| Burning and afterburning of cable insulation (P-07K unit) |
|
| Maximum burning voltage | 40 kV |
| Burning power | 20 kW |
| Output DC voltage: – 3rd level of burning; – 2nd level of burning; – 1st level of burning |
20 kV 6 kV 2 kV |
| Maximum pulse current of the primary winding | 90 А |
| Maximum protection by burning current | 50 А |
| Afterburner voltage | 400 / 250 V |
| Maximum afterburner current | 40 А |
| TP no-load current | 10 А |
| Duration of the operation/rest cycle:: – BURN mode; – AFTERBURNER mode; – other modes |
30 / 30 min. 15 / 30 min. 120 / 30 min. |
| Previous determination of the distance to the place of cable damage (DTDR-100 reflectometer) |
|
| Working mode | TDR (low voltage pulse), ICE (impulse current method) |
| Maximum ranging range | 0…100 km |
| Highest resolution | 0.1 m |
| Measurement error | ± (0.5% × L + 1 m) |
| Ranging blind area | 2 m |
| Signal gain adjustment range | 70 dB |
| Low voltage pulse emission voltage | 30 V |
| Low pressure pulse width | 40 ns…20.5 us |
| Wave speed setting range | 100 m/us…300 m/us |
| Maximum sampling frequency | 400 MHz real-time sampling |
| Pinpointing the exact location of cable damage (GPK-11.1 generator, IAP-06 receiver, PP-4 receiver) |
|
| Operating frequency of the generator | 1515 Hz |
| Generator output power | 1000 W |
| Maximum load current | 40 А |
| Bandwidth of the acoustic method of magnetic synchronization of the RR-4 receiver | full pass: 80…1500 Hz low bandwidth: 80…400 Hz high bandwidth: 200…1500 Hz bandwidth: 150…600 Hz |
| Signal gain | ≥ 80 dB |
| Accuracy | 0.1 m |
| Background noise suppression mode | support, absence and adaptive suppression |
| Display | LCD display, 800 × 470 dots |