CTVan
Cable Test and fault location van

APPLICATION:

  • Testing of insulation of power cables, busbars, insulators and other solid dielectrics with AC and DC voltage.
  • Burning of defective cable insulation with DC voltage with parallel afterburning.
  • Preliminary determination of the distance to the place of cable damage.
  • Precise location of cable faults by induction and acoustic methods.

Description

The CTVan Cable Test and Fault Location Van offers a comprehensive solution designed for testing cable lines within the voltage range of 0.4 kV to 10 kV, accurately providing pinpoint areas of cable faults. Structurally, it encompasses both an operator’s compartment and a dedicated high-voltage compartment.

A distinct control rack serves as the demarcation between the operator’s compartment and the high-voltage section. This control rack hosts essential control components of the electrical laboratory, alongside display elements that facilitate real-time monitoring of test parameter values.

Furthermore, based on the specific preferences and needs of our esteemed Customers, the electrical laboratory can be further enhanced with supplementary equipment, thoughtfully integrated to align precisely with unique requirements.

TECHNICAL SPECIFICATIONS:

AC and DC voltage testing
(VU-50 testing unit)
AC voltage range 50 kV
DC voltage range 60 kV
Accuracy of voltage measurement ±3 %
Output current measuring range 1.0 / 10 mA
Accuracy of current measurement ±5 %
Power 2.5 kW
Burning and afterburning of cable insulation
(P-07K unit)
Maximum burning voltage 40 kV
Burning power 20 kW
Output DC voltage:
– 3rd level of burning;
– 2nd level of burning;
– 1st level of burning
20 kV
6 kV
2 kV
Maximum pulse current of the primary winding 90 А
Maximum protection by burning current 50 А
Afterburner voltage 400 / 250 V
Maximum afterburner current 40 А
TP no-load current 10 А
Duration of the operation/rest cycle::
– BURN mode;
– AFTERBURNER mode;
– other modes
30 / 30 min.
15 / 30 min.
120 / 30 min.
Previous determination of the distance to the place of cable damage
(DTDR-100 reflectometer)
Working mode TDR (low voltage pulse),
ICE (impulse current method)
Maximum ranging range 0…100 km
Highest resolution 0.1 m
Measurement error ± (0.5% × L + 1 m)
Ranging blind area 2 m
Signal gain adjustment range 70 dB
Low voltage pulse emission voltage 30 V
Low pressure pulse width 40 ns…20.5 us
Wave speed setting range 100 m/us…300 m/us
Maximum sampling frequency 400 MHz real-time sampling
Pinpointing the exact location of cable damage
(GPK-11.1 generator, IAP-06 receiver, PP-4 receiver)
Operating frequency of the generator 1515 Hz
Generator output power 1000 W
Maximum load current 40 А
Bandwidth of the acoustic method of magnetic synchronization of the RR-4 receiver full pass: 80…1500 Hz
low bandwidth: 80…400 Hz
high bandwidth: 200…1500 Hz
bandwidth: 150…600 Hz
Signal gain ≥ 80 dB
Accuracy 0.1 m
Background noise suppression mode support, absence and adaptive suppression
Display LCD display, 800 × 470 dots

 

 