CTV-32
Cable Test Van

APPLICATION

  • DC voltage testing up to 32 kV of insulation of power cables, insulators, surge arrestors, etc.
  • Burning faulty cable insulation (optional).
  • Pre-location of the distance of the cable fault using the built-in reflectometer (TDR, ICE, MIM, and Decay methods).
  • Precise pinpointing of cable faults by the induction and acoustic method.

Description

CTV-32 Cable Test Van is a complex solution for preliminary and accurate location of faults in power cables, as well as their subsequent high voltage tests.

CTV-32 offers a comprehensive solution designed for testing cable lines within the voltage range of 0.4 kV to 10 kV, accurately providing pinpoint areas of cable faults. Structurally, it encompasses both an operator’s compartment and a dedicated high-voltage compartment.

A distinct control rack serves as the demarcation between the operator’s compartment and the high-voltage section. This control rack hosts essential control components of the test van, alongside display elements that facilitate real-time monitoring of test parameter values. The rack is also equipped with sliding drawers for storage of additional equipment or tools.

At the request of the Customer, the CTV-32 can be supplemented with additional equipment in accordance with the requirements.

TECHNICAL SPECIFICATIONS

DC voltage testing
(High-voltage unit)
Output DC voltage 0…32 kV
Output Impulse voltage 0…32 kV
Integrated capacitor 4 µF
Maximum energy 2048 J
Pre-location method ICE, MIM, Decay
Impulse period 3…8 s
Discharge auto discharge
Cable drum HV Connection drum 50 m, grounding cable drum 50 m, power supply drum 50 m
Burning of faulty cable insulation (optional)
(BU-60/500 (or BU-60/600) Burning unit)
Maximum output voltage 60 kV
Maximum output current 500 mA (option A)
600 mA (option B)
Mode pure burning (option A)
Burning integrated with voltage drop method pre-location smart bridge (option B)
Pre-location of the distance of the cable fault
(Built-in Digital Time Domain Reflectometer)
Working mode TDR (low voltage pulse),
ICE (impulse current method),
MIM (multiple impulse method)
Decay
Maximum ranging range 0…60 km
Highest resolution 0.1 m
Measurement error ± 0.1 %
Pin-pointing accuracy ±0.2 m
Sampling frequency 250 MHz
LCD Display 17” TFT
Operation system Windows 10
Connection port USB2.0
Language English, Turkey, Ukrainian
Storage 2000 waves
Precise pinpointing of cable faults
(PP-4 Acoustic-Magnetic Pin-pointer)
Bandwidth all-pass: 80…1500 Hz
low-pass: 80…400 Hz
high-pass: 200…1500 Hz
band-pass: 150…600 Hz
Signal gain ≥ 80 dB
Accuracy 0.1 m
Background noise reduction mode support, no and adaptive noise reduction
Display 800 x 470 dot LCD
Power supply 3.7 V, 6700 mAh (built-in Li-ion battery series)
Continuous work time above 9 hours
Charger input 220 V AC ± 10 %, 50 Hz; output 8.4 V, 5 V / 2 A
Dimensions 230 x 127 x 55 mm
Weight 1 kg (main unit), 1.4 kg (sensor)

Download

We use cookies on our website. Some of them are technically necessary, while others help us to improve this website or provide additional functionality. By using it, you agree to our cookie policy.