ETL-10
Mobile electrotechnical laboratory / Cable test van

APPLICATION:

  • Testing of insulation of power cables, busbars, insulators and other solid dielectrics with AC and DC voltage.
  • Burning of defective cable insulation with DC voltage with parallel afterburning.
  • Pre-location of the distance of the cable fault.
  • Precise location of cable faults by induction and acoustic methods.

Description

The ETL-10 is a complex solution for preliminary and accurate location of faults in power cables, as well as their subsequent high voltage tests.

The ETL-10 is mounted in the van and structurally consists of two compartments: the operator’s compartment and the high-voltage compartment. Operator’s compartment is separated from the high-voltage compartment with a control rack, on which the controls of the electric line operation (switches, regulators, etc.) and indication units are placed, to control the test parameter values. The rack is also equipped with sliding drawers for storage of additional equipment or tools.

At the request of the Customer, the ETL-10 can be supplemented with additional equipment in accordance with the requirements.

TECHNICAL SPECIFICATIONS:

AC and DC voltage testing
(BVI-60/50-M5 high-voltage test unit)
Maximum DC voltage 60 kV
Maximum AC voltage 50 kV
Maximum DC current 60 mA
Maximum AC current 70 mA
Burning and afterburning of cable insulation
(BPR-25/8 unit)
Maximum output voltage in idle mode 20 kV
Minimum output voltage in idle mode 1 kV
Number of burn-in steps (5, 10, 15 and 20 kV) 4 pcs.
Maximum current in short circuit mode (5 kV) 2 А
Current consumption (limited by line choke) 63 А
Power consumption 12 kVA
Power delivered to the load in matched mode 3.5 kW
Maximum afterburning voltage in idle mode (“1 kV”) 1500 V
Maximum afterburning current in short circuit mode (“0,5 kV”) 18 А
Pre-location of the distance of the cable fault
(ISKRA-4 reflectometer)
Working mode TDR (low-voltage impuls method),
ICE (high-voltage oscillatory discharge method with current coupling),
Decay (high-voltage oscillating discharge method with voltage coupling),
ARC (high-voltage pulsed method).
Range of the measured distance to the fault location 3 – 15300 m
Resolution 0.5 m
Parameters of high-voltage probing pulses on 30 Ohm load:
– amplitude
– edge duration
– pulse duration
3 – 25 kV
0.15 ms
2 ms
Parameters of low-voltage probing pulses on 30 Ohm load:
– amplitude
– edge duration
– pulse duration
5 V
0.02 ms
0.05 – 10 ms
Maximum working voltage of the pulse voltage probe 60 kV
Precise pinpointing of cable faults
Induction method
(GZCH-2500 generator of audio frequency, P-806 Receiver)
Output power in matched mode 2500 W
Maximum output idle voltage 300 V
Maximum output current 80 А
Generation frequency 1024/2048 Hz
Modulation frequency 1.5 – 3 Hz
Quantity of steps of matching with the load 12
Load resistance range 0.5 – 150 Ohm
Acoustic method
(GAUV-20-16 Generator of acoustic surge waves, P-806 Receiver)
Capacity of accumulator 16 μF
Maximum output voltage 20 kV
Maximum energy of pulse discharge 3200 J
Operation modes manual / automatic
P-806 Receiver
Frequency range 1024 ± 2 / 2048 ± 4 Hz
Magnetic field sensitivity at 6 dB 50 mA
Mode of operation: Bandwidth -3 dB Bandwidth -20 dB
– «1024 Hz»
– «2048 Hz»
– ACUST
9+1 Hz
10+2 Hz
100 – 12000
10+2 Hz
12+4 Hz
Load 16 – 100 Ohm (headphones)

 