HVT-60/80-500
Resonant test system

ADVANTAGES

  • Test voltage current, exciting voltage, resonance indication and monitoring function.
  • Voltage rising interlock when lose resonance.
  • Voltage, regulating speed can be adjusted continuously, little of waveform distortion.
  • Zero position, lower/upper limit, over current, over voltage, breakdown protection function.
  • Light alarm.
  • Back to zero after testing.

Description

Resonant test system HVT-60/80-500 is designed for high-voltage testing of high-capacitance objects such as generator stator windings, busbars, cables etc. The testing can be performed with either a DC or an AC voltage at industrial frequency, in automatic or manual modes.

Technical performance: Using manual button operation, can meet the complex test requirements and repeated for different test products. The display panel uses a 7-inch touch screen with the function of overvoltage and overcurrent protection.

Main features: By setting tripping and over voltage, over current limit value, to protect the test object. It can set the output limits of the high voltage reactor/transformer and the output limits of the excitation transformer. Automatically and manually tune or manually set the reactor compensation, setting the voltage increasing speed as a percentage of the final boost time or in KV/sec according to IEC 60060-1. Detailed status-fault information marked with colored highlights enables accurate fault detection and safe operation of the system. Voltage measurements conform to IEC 60060-1, showing true RMS values or U/√2.

TECHNICAL SPECIFICATIONS

Testing
System rating 60 kV / 500 kVA
Maximum output voltage 60 kV AC / 30 kV AC / 80 kV DC
Maximum output current 8.33 A / 16.67 A
Maximum output capacity 500 kVA
Minimum load capacitance 0.022 mF / 0.088 mF
Maximum load capacitance 0.442 mF / 1.769 mF
Duty cycle 20 min ON, 40 min OFF, 8 cycle per day
Acoustic noise level < 85 dB
Standards compliances IEC 60502, IEC 60840, IEC 60601, IEC 60602,
IEC 60551, GB 12706.3, GB 11017.2 etc
General
Input 380 V ± 10%, 50 Hz, 30.0 kVA
Ambient temperature +5…+40 ℃ (for operating), -10…+50 ℃ (for storage)
Daily mean temperature ≤ 25 ℃
Temperature +15…+25 ℃ for electronic controls and measuring
Relative humidity ≤ 85 % (no condensation)
Altitude ≤ 1500 m
Environment indoors

 